CliQ II Redundancy Module 20A 40A
Redundancy operation with DRP 20A- (40A)
Parallel Operation
When 2 Power Supplies are connected in parallel, they can share the load if the following steps are taken.
Step1. Measure the output voltages at no load from Anode1 to Ground i.e. Voltage Anode1 to Ground of PSU1 and
Voltage Anode2 to Ground of PSU2. If the voltages are not the same, follow Step 2. If they are the same, skip to Step 3.
Step2. . Adjust the output voltages, with the help of VR on the Power Supply front panel market as ADJUST, to the
same level. For e.g. if PSU1 is measuring 24.15Vdc and PSU2 is measuring 24.25Vdc, adjust the output voltage of one
to be the same as the other
Step3. Connect the Power Supply to the end system load and measure the output voltages from A1 to Ground i.e.
Voltage Anode 1 to Ground of PSU1 and Voltage Anode 2 to Ground of PSU2. Ensure that the output voltages are the
same even after the 2 Power Supplies are connected to load. If not, adjust them with the VR available on the front panel.
A tolerance of +/-25mV would be acceptable.
Note
1)
2)
3)
4)
5)
If the output voltage of any Power Supply is higher, it will take the initial load and share the maximum load.
If the output voltages are the same, then an equal load current sharing between the 2 Power Supplies can be
achieved.
The ORing diode must be of an appropriate rating. The rating must be at least 4 times of the output load current
and at least reverse voltage rating of 20Vrr.
The use of a heat sink is advised to ensure the ORing Diode does not overheat.
Recommended Redundancy Module: DRR-20A
www.deltaPSU.com
5
相关PDF资料
DRS-1215 SURGE SUPPRSSR 15A 14OUT RACKMNT
DRS232 SURGE SUPPR NETWORK RJ45/11
DS1200 IC SRAM 1KBIT 4MHZ 10DIP
DS1220AB-100IND+ IC NVSRAM 16KBIT 100NS 24DIP
DS1220Y-100IND+ IC NVSRAM 16KBIT 100NS 24DIP
DS1225AB-70+ IC NVSRAM 64KBIT 70NS 28DIP
DS1225Y-200+ IC NVSRAM 64KBIT 200NS 28DIP
DS1230WP-150+ IC NVSRAM 256KBIT 150NS 34PCM
相关代理商/技术参数
DRR4110 制造商:Knitter-Switch 功能描述:Tube
DRR4116 制造商:knitter-switch 功能描述:Bulk
DRR-80-014 制造商:TDK-Lambda Corporation 功能描述:- Bulk
DR-RDN20 功能描述:DIN导轨式电源 21-28Vin 30Vout 20A Redundancy Module RoHS:否 制造商:Mean Well 产品:Linear Supplies 商用/医用:Commercial 输出功率额定值:960 W 输入电压:180 VAC to 264 VAC, 254 VDC to 370 VDC 输出端数量:1 输出电压(通道 1):48 V 输出电流(通道 1): 输出电压(通道 2): 输出电流(通道 2): 输出电压(通道 3): 输出电流(通道 3): 尺寸:150 mm L x 110 mm W
DR-RDN20_10 制造商:MEANWELL 制造商全称:Mean Well Enterprises Co., Ltd. 功能描述:20A Power Supply Redundancy Module
DR-RDN20_11 制造商:MEANWELL 制造商全称:Mean Well Enterprises Co., Ltd. 功能描述:20A Power Supply Redundancy Module
DRR-DTH 制造商:Hamlin Electronics 功能描述:Reed Switch 制造商:Hamlin Electronics 功能描述:REED SWITCH CO 500VDC 3A 30W 制造商:Hamlin Electronics 功能描述:REED SWITCH, CO, 500VDC, 3A, 30W 制造商:Hamlin Electronics 功能描述:REED SWITCH, CO, 500VDC, 3A, 30W; Contact Configuration:SPDT-CO; Switching Voltage Max:500VDC; Switching Power Max:30W; Contact Current Max:3A; Contact Resistance Max:125mohm; Switch Case:Glass; Operation Ampere Turns Range:50AT to ;RoHS Compliant: Yes 制造商:Hamlin Electronics 功能描述:Change Over Switch
DRR-DTH 45-50 功能描述:SWITCH REED SPDT .5A 45-50 A/T RoHS:是 类别:开关 >> 磁簧 系列:DRR-DTH 标准包装:1 系列:- 类型:模制壳体 电路:SPST-NO 必须的操作范围:- 必须的释放范围:- 最大开关电流 (DC):1A 最大开关电压 (DC):200V 最大开关功率:15W 磁体:包括在内 安装类型:底座安装 端接类型:- 包装:散装